Appendix A CX-10 Modbus Map
Appendix A Modbus Map Page 5
Hardware I/O Registers.
These are all integer (16 bit) types. Function code 3 reads, 16 writes.
Register Read/write permission Detail
1 Read only Opto buffered digital inputs returned as bits 0-7
2
Read only
Spare - returns 0
3
Read only Spare - returns 0
4 Read only Spare - returns 0
5 Read only Spare - returns 0
6 Read only Spare - returns 0
7
Read only Spare - returns 0
8
Read only
Charge/solar panel input. Multiply this number by 0.007326 to obtain volts.
Range is 0 - 30 volts.
9 Read only
Battery voltage. Multiply this number by 0.007326 to obtain volts.
10
Read or write Relay on/off, set as bits 0-7. Write one word to control all 8 relays at the
same time. A 1 turns on a relay, 0 turns it off
11 Read only
Status of opto buffered input 1 (IN1)
12
Read only
Status of opto buffered input 2 (IN2)
13 Read only
Status of opto buffered input 3 (IN3)
14 Read only
Status of opto buffered input 4 (IN4)
15 Read only
Status of opto buffered input 5 (IN5)
16 Read only
Status of opto buffered input 6 (IN6)
17 Read only
Status of opto buffered input 6 (IN7)
18 Read only
Status of opto buffered input 6 (IN8)
19 Read or write Relay 1 on/off. 1 = relay On, 0 = relay Off
20 Read or write Relay 2 on/off. 1 = relay On, 0 = relay Off
21 Read or write Relay 3 on/off. 1 = relay On, 0 = relay Off
22 Read or write Relay 4 on/off. 1 = relay On, 0 = relay Off
23 Read or write Relay 5 on/off. 1 = relay On, 0 = relay Off
24 Read or write Relay 6 on/off. 1 = relay On, 0 = relay Off
25 Read or write Relay 7 on/off. 1 = relay On, 0 = relay Off
26 Read or write Relay 8 on/off. 1 = relay On, 0 = relay Off